1500W? At 12V that’s 125A - That is fucking dangerous! Most sockets are rated at 20A. Most inverters that are >300W use crocodile clips, or preferably screw-down terminal rings. The cable looks way too thin too. That’s a fire waiting to happen…

  • jared@mander.xyz
    link
    fedilink
    English
    arrow-up
    0
    ·
    3 months ago

    Ah, I’m sure the undersized copper coated aluminum wire will be fine, just fine.

    • PhilipTheBucket@quokk.au
      link
      fedilink
      English
      arrow-up
      0
      ·
      3 months ago

      I looked it up, and the recommended cable size for carrying that voltage and amperage is practically the size of the adapter part lol

      • TimLovesTech@badatbeing.social
        link
        fedilink
        English
        arrow-up
        0
        ·
        3 months ago

        In the US you would need #2 [AWG] gauge wire to handle 125amps safely, and that’s just handling the current, nothing to do with proper grounding or anything.

        Also just for reference, many older homes in the US would only have 100 amp service from the pole, meaning this thing is pushing more amps than a whole house potentially.